防火卷帘门侧面和中间的密封应符合有关规范的要求。
The sealing of the side and the middle of the fire shutter door shall meet the requirements of relevant specifications.
墙侧安装:
Wall side installation:
1)建筑物上有预埋件(钢板)时,清除安装基准后,检查预埋件的尺寸、形状、位置是否与安装图纸设计一致。当满足设计要求时,以此作为支架尺寸的安装基准。
1) If there are embedded parts (steel plates) on the building, check whether the size, shape and position of the embedded parts are consistent with the design of the installation drawing after the installation benchmark is removed. When the design requirements are met, it is used as the installation benchmark of bracket size.
2)建筑物上没有预埋件或预埋件不符合安装技术要求时,应增加厚度等于或大于支撑钢板厚度的钢板垫。根据标识位置,安装底座位置应采用安全适用的膨胀螺栓固定,膨胀螺栓不得小于4根,安全系数不得小于防火卷帘门总重量的5倍。安装基准应与支架尺寸垂直。

2) If there is no embedded part on the building or the embedded part does not meet the installation technical requirements, the steel plate pad with thickness equal to or greater than the thickness of supporting steel plate shall be added. According to the mark position, the installation base position shall be fixed with safe and applicable expansion bolts, which shall not be less than 4, and the safety factor shall not be less than 5 times of the total weight of the fire shutter door. The installation datum shall be perpendicular to the support dimension.

安装在墙上:
Wall mounted:
1)如果没有预埋件的建筑,清洗后安装基准,检查是否大小、形状和预埋件的位置符合安装图的设计和满足设计要求,然后以这个为基准的安装支架。
1) If there is no embedded part in the building, install the benchmark after cleaning, check whether the size, shape and location of the embedded part meet the design requirements of the installation drawing, and then install the bracket based on this benchmark.
2)建筑物内有预埋件,安装基准面平整。如果尺寸能满足安装要求,可直接作为乔木的安装基准。
2) There are embedded parts in the building, and the installation datum plane is flat. If the size can meet the installation requirements, it can be directly used as the installation reference of arbor.
3)当支架安装基面位于建筑结构侧表面和柱伸面时,应在结构侧表面设置预埋件;采用安全适用的膨胀螺栓固定,柱的中间面和位置满足安装要求,然后将这两个面作为尺寸支架的安装基准。
3) When the installation base surface of the support is located on the side surface of the building structure and the column extension surface, the embedded parts shall be set on the side surface of the structure; the safe and applicable expansion bolts shall be used for fixation, and the middle surface and position of the column shall meet the installation requirements, and then these two surfaces shall be taken as the installation basis of the dimension support.